Operating commitments
Response times, a shared Slack channel, maintenance notice, an authoritative inventory and hardware fault handling, written into our HGX B300 delivery specification.
Our operating commitments set out in writing how fast we respond, how we keep you informed, how much notice we give and how we handle hardware faults. They are section 15 of our delivery specification, the baseline for every HGX B300 proposal.
The commitments in one table
Each commitment is a figure in minutes, days or months, so you can check what we do against it.
| Commitment | Figure |
|---|---|
| Incident acknowledged and an incident commander assigned | Within 15 minutes |
| Updates while an incident is open | At least every 60 minutes |
| Network operations engaged, at any hour | Within 15 minutes |
| Facility engineering or remote hands engaged | Within 45 minutes |
| Written postmortem after a customer-impacting incident | Within 7 days |
| Notice before high-risk planned maintenance | At least 7 days |
| Inventory and state changes visible to you | Within 5 minutes |
| DDoS scrubbing activated through BGP | Within 5 minutes |
| Edge firewall rule changes | Within 1 business day |
| Operational telemetry kept, and incident and state history | 30 days, and 12 months |
We do not publish uptime percentages. We publish what we do when something goes wrong, and how quickly.
Support: a shared channel and a named owner
You work directly with the people who run your cluster, in a shared Slack channel that is open at all times.
A shared Slack channel
Open at all times, with our incident commander, network operations, facility operations and remote hands in it.
A named technical account owner
One named person at 1Legion who owns your account.
Two ways to reach on-call
Two independent, tested ways to reach a qualified on-call responder, 24 hours a day, every day.
The channel puts the people affected by an issue and the people who fix it in one place. The second, independent route to on-call is there for the case where the first one is the problem.
Incidents, from first alert to postmortem
Incidents follow one sequence: acknowledgment and an incident commander within 15 minutes, engineers engaged, updates at least every 60 minutes, and a written postmortem within 7 calendar days of every customer-impacting incident.
Acknowledge
We acknowledge the incident and assign an incident commander within 15 minutes. The incident commander is the one person who coordinates the response.
Engage
Network operations are engaged within 15 minutes at any hour, and facility engineering or remote hands within 45 minutes.
Update
You receive updates at least every 60 minutes while the incident is open.
Postmortem
Within 7 calendar days of every customer-impacting incident, you receive a written postmortem.
A postmortem is a written account of an incident: what happened, why it happened and what is being done so it does not happen again.
Maintenance, change and inventory
Planned work that carries risk is announced at least 7 calendar days ahead, changes go through written change management, and an authoritative inventory records your cluster down to the cable.
Maintenance notice
The notice applies to high-risk, non-emergency maintenance, and gives you time to move jobs or take a checkpoint before the work starts. Emergency work is outside the notice period. On the facility side, we ask the data centers we use for 14 days' notice of risky maintenance.
Change management and access
Written change management means changes to your cluster follow a documented process and leave a written record. Out-of-band access, the management path that reaches a server through its BMC, below the operating system, is audited.
The inventory
We keep an authoritative inventory of every rack, node, GPU, NIC, drive, switch, port, transceiver and cable, with a machine-readable export for you. State changes are visible within 5 minutes. Drift detection compares the cluster with the agreed baseline, so a change nobody planned shows up.
We are building our own platform software for inventory, monitoring and burn-in automation, on open-source components. A customer portal and a public API are part of that work and are not available yet.
Hardware fault handling
We find and fix hardware, facility, cooling and fabric faults, and we quarantine a GPU with a fatal fault immediately.
| Fault | What it means | What we do |
|---|---|---|
| XID 79 | The GPU has fallen off the bus and stopped responding | Quarantine immediately |
| XID 48 | The driver has reported a double-bit ECC error | Quarantine immediately |
| Double-bit ECC error | An uncorrectable error in GPU memory | Quarantine immediately |
| Row remapping failure | The GPU could not remap a faulty memory row to a spare | Quarantine immediately |
| Recurring XID 13 or XID 31 | A graphics engine exception or a GPU memory page fault | Act after an agreed count |
| NVMe drive wear | Flash drives wear as data is written to them | Replace before endurance limits |
| NCCL hang | A collective operation stops making progress | Correlate with fabric events |
| Suspected silent data corruption | Wrong results with no error reported | Hold the node in quarantine |
Quarantine takes the affected hardware out of service until the fault is fixed, so no job lands on it. XID 13 and XID 31 can come from the application rather than the GPU, so we act on them when they recur past an agreed count. When an NCCL job hangs, we check fabric events from the same moment, so a link or switch fault behind the hang can be found. Silent data corruption is among the hardest faults to see, because nothing reports it, which is why a suspected node stays in quarantine. NVMe drives are replaced before they reach their endurance limits, rather than after they fail.
Storage appliance service
If your cluster uses a vendor-managed storage appliance, the specification commits to a vendor-supported design with 24/7 escalation, committed throughput and latency per tier, visible usage and quotas, and tested recovery.
- Vendor-supported design. The appliance, from VAST Data, WEKA or DDN, is built to a design its vendor supports.
- 24/7 escalation. A storage issue can be escalated at any hour.
- Throughput and latency per tier. Each storage tier has committed throughput and latency, so you can plan jobs and checkpoints against known figures.
- Usage and quotas. Usage and quotas are visible, so capacity does not run out unnoticed.
- Tested recovery. Recovery is tested, not only documented.
Both storage options, the appliance and storage nodes for your own software, are described on our storage and networking page.
Telemetry and history
We collect hardware telemetry out of band, and keep operational telemetry for at least 30 days and incident and state history for at least 12 months.
Out-of-band telemetry comes from the servers' BMCs through Redfish, so it keeps reporting when the operating system does not. Network and facility telemetry are collected where available. At least 12 months of incident and state history means a fault that recurs months apart can still be traced to its earlier occurrences.
Before any of this applies, every cluster passes the tests on our burn-in and acceptance page. If you also want us to run the platform layer on your servers, see managed Kubernetes.
Questions buyers ask
Is this an SLA with an uptime percentage and service credits?
No. We do not publish uptime percentages or service credits. We publish the commitments on this page instead: response times, update intervals, notice periods, reporting and fault handling. Your proposal sets out the terms of your contract.
How fast do you respond to an incident?
Incidents are acknowledged and an incident commander assigned within 15 minutes. Network operations are engaged within 15 minutes at any hour, and facility engineering or remote hands within 45 minutes.
How do we reach you outside business hours?
Through the shared Slack channel, which is open at all times, or through two independent, tested ways to reach a qualified on-call responder, 24 hours a day, every day.
How much notice do you give before maintenance?
At least 7 calendar days for high-risk, non-emergency maintenance.
What happens when a GPU has a fatal fault?
We quarantine fatal GPU faults immediately: XID 79, XID 48, double-bit ECC errors and row remapping failures. Then we find and fix the fault.
Tell us what you need to run.
Share the hardware, the number of servers, the term and the start date. You receive a written proposal built on our delivery specification.