Storage and networking

At least 1 TB of usable storage per GPU, a dedicated north-south network, two transit providers, DDoS scrubbing and your own IP space and ASN, all set out in our delivery specification.

GPU cluster storage and networking at 1Legion is specified as tightly as the GPUs: storage sized per GPU, a dedicated north-south network, a redundant internet edge with DDoS scrubbing, and room for your own addresses and ASN. Every figure on this page comes from our delivery specification for HGX B300 clusters, and your proposal lists any numbered deviations. For other servers, storage and networking are configured to your requirements and confirmed in your proposal.

Two storage options

Choose a vendor-managed storage appliance or storage nodes that run your own software; both are sized by the number of GPUs in the cluster.

Option A: storage applianceOption B: storage nodes
What you getA vendor-managed appliance from VAST Data, WEKA or DDN, as you preferStorage nodes for your own storage software
CapacityAt least 1 TB usable per GPUAt least 3 TB raw per GPU
DrivesThe vendor's supported design30.72 TB NVMe PCIe 5.0, self-encrypting drives supported
Reference sizes512 TB, 1,024 TB and 2,304 TB usable for 64, 128 and 288 nodes9, 17 and 38 nodes, with a minimum of 9
Service24/7 vendor escalation, committed throughput and latency per tier, visible usage and quotas, tested recoveryWe run the hardware and replace NVMe drives before their endurance limits; you run the storage software

Raw capacity is counted before your storage software's data protection; usable capacity is what the appliance delivers after the vendor's. Option A suits teams that want one vendor accountable for throughput, latency and recovery. Option B suits teams that already operate their own storage software and want the drives and nodes, not a managed system.

Each GPU node also carries its own NVMe: at least 9.2 TB raw for local data, more than four times the node's 2.1 TB of GPU memory, plus two mirrored 1 TB boot drives (preferred). Burn-in test HW-3 covers GPUDirect RDMA and storage smoke tests, including NVMe read and write.

For training, checkpoint size and frequency set the write throughput you need. Why long-duration training runs fail on shared cloud covers storage I/O and checkpointing on long runs.

North-south network

The north-south network connects every node to storage, CPU services and the edge, and like the GPU fabric it carries only your traffic.

  • Per node: 400 Gb/s preferred, 200 Gb/s minimum, through NVIDIA BlueField-3 frontend NICs at 2 x 400 Gb/s (preferred) or 2 x 200 Gb/s.
  • Oversubscription: none on storage leaves, so their uplinks match the bandwidth of every port below them; below 4:1 on GPU leaves.
  • Protocols: RoCEv2 capable, so storage and service traffic can use RDMA over routed Ethernet, with MTU 9000 jumbo frames.
  • Tenancy: dedicated to one customer, and separate from the east-west GPU fabric described on GPU clusters.

Internet edge and DDoS protection

Your cluster reaches the internet through two independent transit providers and two redundant edge routers, with DDoS scrubbing that activates through BGP within 5 minutes.

100 Gb/s Per transit circuit, from each of two providers
1 min Failover between transit paths, at most
5 min To activate DDoS scrubbing through BGP
1 Tb/s Minimum DDoS scrubbing capacity
  • Transit: two independent providers at 100 Gb/s per circuit, on physically diverse paths, so a single fiber cut does not take down both.
  • Routing: eBGP with BFD, so a failed path is detected and traffic fails over within a minute.
  • Edge routers: two, redundant, on A and B power.
  • Edge ACLs: written to your rules, with changes made within one business day.
  • DDoS protection: volumetric layer 3 and 4 scrubbing from an established provider, activated through BGP within 5 minutes, with at least 1 Tb/s of capacity.

NAT and public addresses

Outbound traffic leaves through a redundant NAT pair on addresses only you use, and inbound services get dedicated public addresses that fail over within 5 seconds.

NAT and egress

A redundant high-availability NAT pair handles at least 10 million concurrent sessions on dedicated SNAT addresses, typically four, so partners can allow-list your outbound traffic by address.

Public service addresses

You get dedicated public addresses, typically eight, and can advertise your service VIPs over BGP, with failover within 5 seconds. IPv6 runs dual stack alongside IPv4.

Bring your own IP space and ASN

If you hold your own IP space and ASN, our edge can advertise them, so your services keep the addresses your users and partners already know.

  • Your prefixes and ASN: the edge advertises customer-owned prefixes and your ASN.
  • RPKI: route origin authorizations (ROAs) for your prefixes are honored.
  • Session security: BGP sessions are authenticated.

Network telemetry

Both edge routers export flow records to your collector in NetFlow v9 or IPFIX, so your network and security teams see what crosses the edge.

We also collect out-of-band hardware telemetry over BMC and Redfish, and network and facility telemetry where available. Operational telemetry is kept for at least 30 days, and incident and state history for at least 12 months. Security and compliance covers access control and our audited out-of-band access, and operating commitments lists every response time.

What the rate covers

The rate covers the servers and the networks that connect them. Storage and the nodes around the GPUs are priced as their own lines, so you pay for what your design uses.

ItemWhere it appears
GPU servers, with their CPUs, memory, NVMe drives and network cardsIncluded in the rate
Fabric on HGX B300 clusters, 800 Gb/s per GPUIncluded in the rate
North-south network, built to the delivery specificationIncluded in the rate
Edge network: two transit providers, redundant edge routers, dedicated public addresses and DDoS scrubbingIncluded in every HGX B300 cluster
Internet bandwidth set in your proposal, with no egress feesIncluded in the rate
Storage appliance from VAST Data, WEKA or DDN, or storage nodesIts own line in your proposal
Local NVMe beyond the server's standard drivesIts own line in your proposal
CPU and control plane nodesTheir own lines in your proposal
More bandwidth, and network designs beyond the delivery specificationPriced in your proposal

How to buy explains terms, billing and the rest of what a proposal contains.

Questions buyers ask

Which storage vendors do you offer?

VAST Data, WEKA or DDN as a vendor-managed appliance, as you prefer, or storage nodes that run your own storage software.

How much storage comes with an HGX B300 cluster?

At least 1 TB usable per GPU on the appliance, which is 512 TB for a 64-node cluster, or at least 3 TB raw per GPU on storage nodes. Each GPU node also has at least 9.2 TB of raw local NVMe.

Do you charge egress fees?

No. Clusters are billed at one fixed rate for the term, with no egress fees.

Can we bring our own IP addresses and ASN?

Yes. The edge can advertise your prefixes and your ASN, honors RPKI ROAs and authenticates BGP sessions.

How quickly does DDoS protection start?

Volumetric layer 3 and 4 scrubbing activates through BGP within 5 minutes, with at least 1 Tb/s of capacity.

Does this apply to every server?

It applies to HGX B300 clusters built to our delivery specification. For other servers, storage and networking are configured to your requirements and confirmed in your proposal.

Tell us what you need to run.

Share the hardware, the number of servers, the term and the start date. You receive a written proposal built on our delivery specification.